The component cooling water system is a nonsafety-related, closed-loop cooling system that transfers heat from various plant components to the service water.

Water cooled chiller
WT-240,300,360

Temp. Range

5~40°C

Humidity Range

40~80%

Cooling Capacity

56~105 KW

Features

  • High inductive temperature control switch, easy control the manufacturing process liquid temperature. (accuracy ±0.5 ℃)
  • With Euro-well-known brand compressor and water pump, low noise, high E.E.R
  • Casing pipe type condenser and stainless steel plank type heat exchanger. Significantly promote the cooling efficiency.
  • The cold storage trough can store surplus energy according to the demand. Can save 20% energy.
  • Microprocessor control panel and auto-detect indicate lamp.
  • With perfect and multiple security protected device, postponed and automatic return home circulated function.
  • Stainless Steel water tank and water circulating system design.
  • Can set water supply by manual or automatic method.
  • With perfect anti-shock device and feet wheel design, easy to move.
  • Must collocate with cooling water tower.

Appliations

Injection machine, Blow molding machine, Semiconductor, Faceplate, Co-extruder machine, Laminating extrusion, Printing, UV, Ink roller, High-cycle, Foam, Ultrasonic, Food, Chemistry, Medical, Hydraulic press machine etc. All kinds of industrial equipment.
  • The plastic hollow molding/ plastics runner film roller cooling
  • Plastic injection and punching molding cooling.
  • All kind microprocessor control machine tools, grinders, machine centers and combined lathe of the principal axis lubrication and hydraulic system cooling.
  • Laser cutting & marking machine.
  • Semiconductor and electron Instruments, ultrasonic cleaning equipment.
  • All kind of machine processes liquid cooling.

Specifications

Model WT-240B
Temp. range 5~40°C(Indoor )
Humidity range 40~80%
Power 3P –220/380V –50/60Hz
Coolant R407
Cooling liquid Industrial Pure Water
Export temp 8~30°C ± 1°C
Cooling capacity
50/60Hz
Kcal-h 48,000/60,000
BTU-h 192,000/240,000
kw 56/70
Pump 50/60Hz HP 3.5 / 5.0
Water flow L/min 380
Water pressure Kg 2.5
Water piping High pressure rubber tube, Stainless steel piping
Protection system No fuse magnetic switch, water level, against/lack phase, ultra-temp., overload protection
Compressor HP 20
Cold-water inlet/outlet 2”
Remote control AC220V、DC24V
Color Black+White
Dimension LxWxH mm 1,770 x 1,050 x 1,940
Water tank L 600
Weight kg 960

Also have the AT-A2, AT-AL, AT-AL2 system further for your choice.
We reserve the right that modification designs and technique parameter change and will not notice specially.

Model WT-300B
Temp. range 5~40°C(Indoor)
Humidity range 40~80%
Power 3P –220/380V –50/60Hz
Coolant R407
Cooling liquid Industrial Pure Water
Export temp 8~30°C ± 1°C
Cooling capacity
50/60Hz
Kcal-h 60,000/75,000
BTU-h 240,000/300,000
kw 70/87
Pump 50/60Hz HP 5.5
Water flow L/min 380
Water pressure Kg 2.5 / 3.0
Water piping High pressure rubber tube, Stainless steel piping
Protection system No fuse magnetic switch, water level, against/lack phase, ultra-temp., overload protection
Compressor HP 25
Cold-water inlet/outlet 2”
Remote control AC220V、DC24V
Color Black+ White
Dimension LxWxH mm 1,770 x 1,050 x 1,940
Water tank L 750
Weight kg 1,050

Also have the AT-A2, AT-AL, AT-AL2 system further for your choice.
We reserve the right that modification designs and technique parameter change and will not notice specially.

Model WT-360B
Temp. range 5~40°C(Indoor)
Humidity range 40~80%
Power 3P –220/380V –50/60Hz
Coolant R407
Cooling liquid Industrial Pure Water
Export temp 8~30°C ± 1°C
Cooling capacity
50/60Hz
Kcal-h 72,000/90,000
BTU-h 288,000/360,000
kw 84/105
Pump 50/60Hz HP 5.5 / 8.0
Water flow L/min 430
Water pressure Kg 2.5 / 3.5
Water piping High pressure rubber tube, Stainless steel piping
Protection system No fuse magnetic switch, water level, against/lack phase, ultra-temp., overload protection
Compressor HP 30
Cold-water inlet/outlet 2”
Remote control AC220V、DC24V
Color Black+White
Dimension LxWxH mm 1,770 x 1,050 x 1,940
Water tank L 750
Weight kg 1,320

Also have the AT-A2, AT-AL, AT-AL2 system further for your choice.
We reserve the right that modification designs and technique parameter change and will not notice specially.

Freshwater or central cooling system: Fresh water is used in a closed circuit to cool down the engine room machinery. The fresh water returning from the heat exchanger after cooling the machinery is further cooled by sea water in a sea-water cooler.
As discussed above, in the central cooling system, all the working machinery on ships are cooled down using circulating fresh water. This system comprises of three different circuits